UPS runtime estimator

Estimate outage runtime from battery specifications and actual network load, while checking both W and VA ratings.

1. Battery and load

Total number of identical batteries
Conservative factor for age and high discharge

2. Estimate

Estimated runtime—
Hours—
Estimated usable energy—
Recommended minimum—
W rating check
VA rating check
Important: This is a simple energy model. Lead-acid batteries deliver less than rated Ah at high loads; temperature, age and UPS cutoff voltage also matter. Prefer the manufacturer runtime curve for a specific model.

Formula

Nominal Wh = V × Ah × battery count
Usable Wh = nominal Wh × inverter efficiency × usable battery factor
Estimated hours = usable Wh ÷ load W

How to separate VA, W and runtime when choosing a UPS →

Worked example

Two 12 V 9 Ah batteries, a 40 W load, 85% efficiency and 70% usable factor yield 128.5 Wh and about 3.2 hours in the simple model. Treat this as a comparison estimate, not guaranteed runtime; check the candidate's manufacturer runtime chart at 40 W first.

Next action by result

  • W or VA fails: reject the unit and choose one with margin in both ratings.
  • Runtime fails: remove nonessential loads or consider a supported external battery.
  • Estimate passes: perform a controlled outage test after a full charge and verify shutdown behavior.

Limits: age, temperature, Peukert effect, cutoff voltage and UPS self-consumption differ from the simple model. Do not use this estimate alone for life-safety equipment.